Rheem Error Codes

Rheem Tankless Error Codes

Tankless Systems are complicated, thus, they can have some errors and electronic issues resulting in Rheem error codes for the tankless. We have put together a thorough list of Rheem error codes to help you diagnose and potentially fix any issues you and your tankless may have.

 

CODEFaultRheem Error Code Remedy
001 Hour continuous combustionClose all hot water taps to reset unit.

Turn off, or remove circulation pumps (unit is not designed for continuous

operation with circulation systems).

05Imperfect Combustion AlarmClean air inlet filter.

Clean combustion air fan.

Clean heat exchanger fins.

Check for adequate combustion air ventilation openings and clean if necessary.

Check vent system for partial blockage and correct as necessary.

10False flame detectionCheck all vent components for proper connections.

Check that nothing is blocking the flue inlet or exhaust.

Ensure proper venting materials were used.

Ensure condensation collar was installed correctly.

Ensure heat exchanger fins, fan, and air intake are not blocked.

11No IgnitionEnsure you have gas to the appliance.

Ensure gas type and pressure is correct.

Bleed all air from gas lines.

Ensure gas line, meter, and regulator are sized properly.

Ensure appliance is properly grounded.

Check gas solenoid valves for open or short circuits.

Ensure igniter is operational.

Check igniter wiring harness for damage.

12Flame FailureEnsure you have gas to the appliance.

Ensure gas type and pressure is correct.

Bleed all air from gas lines.

Ensure flame rod wire is connected.

Check flame rod for carbon build-up.

Ensure gas line, meter, and regulator are sized properly.

Ensure appliance is properly grounded.

Check gas solenoid valves for open or short circuits.

Check power supply for loose connections.

Check power supply for proper voltage and voltage drops.

Disconnect remote control.

Disconnect and re-connect all wiring harnesses on unit and PC board.

Ensure proper venting material was installed.

Ensure condensation collar was installed properly.

Ensure maximum vertical vent length does not exceed allowable limits.

Ensure maximum horizontal vent length does not exceed allowable limits.

14Overheat Wrap FaultEnsure high fire and low fire manifold pressure are correct.

Check gas type of unit and ensure it matches gas type being used.

Check heat exchanger for cracks and/or separations.

Ohm out safety circuit.

Check for improper conversion of product.

Check for restrictions in air flow around unit and vent terminal.

Check for a foreign materials in combustion chamber and/or exhaust piping.

15Boiling Safety DeviceCheck for closed water heater inlet valve or restrictions in cold water inlet pipe

(must be fully open).

Check for clogged heat exchanger (scale buildup).

On commercial water heater, lower setpoint temperature below 180F at high

altitude.

16Over Temperature WarningCheck for clogged heat exchanger.

Check for restrictions in air flow around unit and vent terminal.

Check for a foreign materials in combustion chamber and/or exhaust piping.

21Malfunction of Air Intake Filter SwitchMake sure air filter door is properly seated.

Make sure front panel is properly installed.

24Malfunction of Operational SwitchPress max button on PCB to reset.

Press min button on PCB to reset.

Replace PCB

29Heat Exchanger Outlet Temp. Too LowClean heat exchanger air inlet
31Water Inlet Temperature Sensor FaultCheck sensor wiring for damage.

Ohm out sensor

Check and clean scale from sensor.

Replace sensor.

33Outgoing Water Temperature Sensor FaultCheck sensor wiring for damage.

Ohm out sensor

Check and clean scale from sensor.

Replace sensor.

34Combustion Air Temperature Sensor FaultCombustion Air

Temperature Sensor Fault

35Improper Thermistor ConnectionsCheck that all thermistors are connected to propor connections on PCB.
51Gas Inlet Solenoid Valve FaultCheck gas inlet solenoid valve wiring harness for loose or damage terminals.

Ohm out solenoid valve.

52Modulating Solenoid Valve FaultCheck modulating gas solenoid valve wiring harness for loose or damage

terminals.

Ohm out solenoid valve.

61Combustion Fan FailureEnsure fan motor will turn freely. (Motor will operate with a small amount of

restriction.)

Check wiring harness to motor for damaged and/or loose connections.

Ohm out motor winding.

71Gas Inlet Solenoid Valve Control FaultCheck gas inlet solenoid valve wiring harness for loose or damage terminals.

Ohm out solenoid valve.

Replace PCB

72Flame Sensing Device FaultEnsure flame rod is touching flame when unit fires.

Check inside burner chamber for any foreign material blocking flame at flame

rod.

Check all wiring to flame rod for damage.

Check flame rod for proper voltage.

Remove flame rod and check for carbon build-up, clean with sand paper.

Replace flame rod.

76Communication Fault with Remote ControlCheck remote control wiring for loose or damaged connections.

Bypass remote control cable by connecting remote control directly to remote

control terminals on PCB. Replace cable if found to be faulty.

Replace remote control.

Replace PCB.

79Fan Motor Current FaultrEnsure fan motor will turn freely. (Motor will operate with a small amount of

restriction.)

Check fan motor for proper voltage.

Replace fan motor.

Replace PCB.

80,81Gas Cut-off FailureOhm out all solenoid valves.

Check voltage of all flame rods.

Replace gas control valve.

82Gas type data failureProgram PCB for proper gas type.
99Blocked Flue FaultClean any blockage in heat exchanger, combustion fan, inlet filter, and exhaust

flue.

No CodeNothing happens when water is flowing through unit.Make sure unit is connected to proper power supply and circuit breakers are on.

Make sure power supply inlet fuses are not blown.

Clean inlet water supply filter.

Ensure you have at least the minimum flow rate required to fire unit.

Check for pipe dope inside water flow control turbine.

On new installations ensure hot and cold water lines are not crossed.

Check for bleed over. (Close cold water supply valve to water heater. Open hot

water taps at fixtures. If water flows steady from hot water taps, there is a bleed

over in the system.)